Input signal type | Ⅱ standard signal: (0 ~ 10) mA, (0 ~ 5) V |
Ⅲ standard signal: (4 ~ 20) mA, (1 ~ 5) V | |
14 thermocouples: B, E, J, K, S, T, R, N, WRe5-26, WRe3-25, BA1, BA2, F1, F2 | |
3 kinds of thermal resistance: Pt100, Cu50, JPt100 | |
Other signals (0-20) mv, (0-100) mv, (-10-10) v, (0-10) v, (-5-5) v, (0-1) v, ) V, resistance 0-350Ω, frequency 0-10KHZ | |
Isolation | Isolation between channels and ground Resistant to heat greater than 500VAC, isolation between channels and channels Withstanding voltage> 250VAC |
Powered by | Voltage (100 ~ 240) VAC |
Frequency (47 ~ 63) Hz | |
The maximum power consumption 30VA | |
Fuse specifications | 3A / 250VAC, slow blow type |
Distribution output | Each loop 65ma, 24VAC, up to 8 loops |
Alarm output | Up to 24 channels, 250VAC, 3A normally open relay contacts |
Simulated transmission output | Up to 8 Road 4-20ma transmission output |
Hardware watchdog | Integrated WATCHDOG chip, to ensure long-term safe and reliable host operation |
Real time clock | Using hardware real-time clock, power-down by the lithium battery, the maximum clock error ± 1 minute / month |
Power-down protection | All data is saved in NAND FLASH memory, ensuring that all historical data and configuration are lost due to power loss |
Communication Interface | Provide RS-485 and RS232 two kinds of communication interface for users to choose, can be Ethernet connection, but also with the panel printer connection |
Protocol | Using R-Bus or ModBus protocol, the communication baud rate has 5 options, 1200 bps, 9600 bps, 19200 bps, 57600 bps and 115200 bps |
The sampling period | 1 second, that is, 1 second on each channel are sampled once |
Record interval | 1S, 2S, 5S, 10S, 15S, 30S, 1min, 2min, 4min optional |
Display | 10.4 inches 640 * 480, 64 color TFT true color liquid crystal display |
Size | Overall dimensions 288mm * 288mm * 244mm, hole size 282mm * 282mm |
Brightness | 0 ~ 100% adjustable |
Alarm display | Up to 256 alarm displays can be displayed |
Alarm type | Upper limit alarm, upper limit alarm, lower limit alarm, lower limit alarm |
Accuracy class | Numerical accuracy of 0.2% FS |
Curve accuracy 0.5% FS | |
Data retention period | About 10 years |
1. Cost-effective
Super multi-channel design, support for all types of signals
CCFL backlight display, data clearer observation
2.Product warranty
From production to delivery, each product has been tested 5, Cengcengbaguan to ensure that the interests of users
3.Customer trust
Supmea focused on automation for 17 years, the product has a complete patent certificate, access to 60 million users of the support and recognition.